Harbin East Alarm Equipment Development Co., Ltd.
Main products:Alarm,Gas Analyzer,Gas Detector 200A8-XF1,Gas Detector 200A9,Gas Detector 200A9-FS
Products
Contact Us
  • Contact Person : Ms. Gui Teresa
  • Company Name : Harbin East Alarm Equipment Development Co., Ltd.
  • Tel : 86-451-82380878
  • Fax : 86-451-82380879
  • Address : Heilongjiang,Harbin,No.119, Fushui Road, Nangang District
  • Country/Region : China
  • Zip : 150090

HOT! Online explosion-proof ozone monitor for industrial and hazardous locations application

HOT! Online explosion-proof ozone monitor for industrial and hazardous locations application
Product Detailed
Imported sensor 2+2 digits LED display loud sound of 90dB Practical new-technique patent - over-concentration protection

Online explosion-proof ozone monitor

Characteristics  (GQB-200A8  Gas detector alarm)

90dB high bright LED display screen, clearly seen outside 10 meters.

Sensor imported with original packaging.

double windows and 2+2 digits display.

material of aluminium magnesium alloy.

sensor exchanged needless calibration.

specialized technique can make the sensor life doubled

Certificates 

one patent of practical new technique.two patents of appearance technique.fire control type approval of the ministry of public security.National explosion-proof electric inspection.

Technical parameters (combustible gas)

Type of sensor

Catalytic combustion sensor

Working voltage

DC24V±5V

electric signal output

4-20mA

display

2+2 digits LEDdisplay; 3-colors LED light

Relay output

24V/1A

kinds of Gas detection

Combustible,Oxygen and toxic gas

Detection range

0-100% LEL

Response time

<15S

Detection precision

3%

Zero drift

2% per year

Lifetime

>3 years

Enable application areas

1&2 hazardous zones of explosive gas

sound & light alarm

100dB red color alarm

Relative humidity

 10~95%RH ( no condensation)

Atmospheric pressure

86~106Kpa

Operating temperature

-40ºC~ +70ºC

Transmission cable

3 core shielding line with 1~1. 5mm2 diameter

Electrical equipment connector

M20*1.5 (cast Al);   G3/4”(stainless steel)

Explosion-proof grade

Exd II CT6

Weight

2.5kg(cast Al); 4kg(stainless steel)

Kinds of Gas Detection

detection accuracy

mesurement range

operating temperature

O2

0.50%

0-30%

-20-50°C

NH3

1ppm

0-100ppm

-20-40°C

CO

1ppm

0-100ppm

-20-50°C

CL2

0.1ppm

0-10ppm

-20-50°C

C2H4O

1ppm

0-100ppm

-20-50°C

H2(ppm)

1ppm

0-100ppm

-20-50°C

H2(LEL)

100ppm

0-10000ppm

-20-40°C

H2(1%)

1ppm

0-1%

-20-40°C

HCL

1ppm

0-30ppm

-20-40°C

H2S

1ppm

0-100ppm

-20-50°C

NO

1ppm

0-100ppm

-20-50°C

NO2

0.1ppm

0-10ppm

-20-50°C

SO2

1ppm

0-20ppm

-20-50°C

C2H3CL

1ppm

0-100ppm

-20-50°C



Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.